Storingen


Ketel type Cadet CDN100

Storingscode n04

Oorzaak:

The fan speed is being limited due to the flue temperature exceeding 215°F.

Oplossing:

- Inspect the heat exchanger. 
- Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor. Replace the sensor if necessary. 
- Verify that the vent/air intake pipes are properly installed and that there are no obstructions. 
- Replace the main control board.