nl en de
Selecteer uw gewenste taal

In welk land bevindt uw cv ketel zich?

Storingen


Ketel type Cadet CDN100

Storingscode b05

Oorzaak:

The flue temperature has exceeded 240°F.

Oplossing:

- Inspect the heat exchanger. 
- Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor. Replace the sensor if necessary. 
- Verify that the vent/air intake pipes are properly installed and that there are no obstructions. 
- Replace the main control board.