Boiler type UBSSC-050

Error code E51

Cause:

Supply temperature sensor is open. No continuity.

Solution:

1. Is harness plugged into supply water sensor? 
Is harness plugged into control module J5?
Yes: -> 2
No: Insert harness 

2. Disconnect J5 from control module. Using digital meter measure check continuity of white wires between control board and sensor. Continuity? 
Yes: -> 3
No: -> Replace wires 

3. Unplug J5 connector on control board. Using digital meter measure resistance between terminals J5-11 and J5-3. Estimate sensor temperature. Does it fall in the range of the resistance chart? 
Yes: Replace control module
No: Replace supply water sensor.