nl en de
Select your language

Select country

Errors


Boiler type UBSSC-050

Error code E44

Cause:

Boiler is powered by three wires, hot, neutral and ground. E44 displays when neutral wire isnot neutral.

Solution:

1. Measure incoming power with volt meter. Is terminal 120 VAC (L) approximately 120 VAC? Is 120 VAC (N) approximately 0 VAC?
Yes: -> 2 
No: Correct power supply to boiler.

2. Verify order of pins on J2. Pin order should be: empty, black (or red), white, green. Measure volt on pins of black wire and white wire. Is wiring/pins in right order? Does black/wire have 120 VAC? Does white wire/pin have 0 Vac? 
Yes:Replace control module. 
No: Replace wire Harness.