Boiler type Evolution EVS-2500

Error code Comm Failure

Cause:

Communication Failure The Modbus or Peer-To-Peer network has failed. When the Modbus network fails the following control mode changes are taken automatically:

Selected Modes                                Resulting Control Mode           Modbus Mod                                    Outlet Sensor and Local Setpoint Modbus Mod & Remote Sensor             Remote Sensor and Local Setpoint Modbus SP                                      Outlet Sensor and Local Setpoint Modbus SP & Remote Sensor               Remote Sensor and Local Setpoint

After a Modus communication failure, the ‘Comm Failure’ alarm is not cleared until communication is restored and successfully writes to both the Remote On / Off Modbus Command (00004) and Remote Firing Rate or Remote Setpoint (40006) points have been completed, power is cycled or the protocol parameter is changed to Peer-To-Peer and then back to Modbus.

When a Peer-To-Peer network has failed the boilers begin operation as stand alone boilers using the selected parameters.

After a Peer-To-Peer communication failure the ‘Comm Failure’ alarm is not cleared until communication is restored and the boiler rejoins a network with at least one other boiler, power is cycled or the protocol parameter is changed to Modbus and then back to Peer-To-Peer.

Solution:

Confirm each boiler has a unique address Check Wiring and Remote System