Boiler type Evolution EVS-2500

Error code Remote Input Fail

Cause:

Remote Control Input Fail The Remote Control Input is configured and is not connected or is above or below a valid range. When the remote control input fails, the following control mode changes are taken automatically:

Selected Modes                                 Resulting Control Mode

Remote Mod                                     Outlet Sensor and Local Setpoint
Remote Mod & Remote Sensor              Remote Sensor and Local Setpoint
Remote SP                                       Outlet Sensor and Local Setpoint
Remote SP & Remote Sensor                Remote Sensor and Local Setpoint                  

 





 

      

Solution:

Check Wiring and Remote System