Storingen


Ketel type IPW050DW

Storingscode Low Outlet Water Temp

Oorzaak:

1 Modulating valve lost calibration

2 Boiler water supply temperature or flow has dropped below requirement to satisfy demand

3 Control module not supplying 0 - 10 VDC control signal to valve

4 Modulating valve is not in AUTO Mode

5 No 24 VAC power supplied to modulating valve

6 Heat exchanger is improperly sized for load

7 Heat exchanger scaled on boiler side

8 High limit is tripped

 

Oplossing:

1 - Remove cover on modulating valve electronics and press the recessed calibration button to re-calibrate the valve

2 - Ensure ball valves are open fully. - Ensure boiler water flow matches what is specified in the sizing table. - Ensure boiler side Y strainers are not clogged.

3 - Ensure the valve is wired correctly by referencing the wiring diagram on page 28 of this manual.

4 - Rotate valve handle until it is in AUTO Mode

5 - Ensure the valve is wired correctly by referencing the wiring diagram on page 28 of this manual. - Ensure the transformer is connected to the harness correctly and its built-in circuit breaker has not tripped

6 - Reduce load on heat exchanger or re-size heat exchanger.

7 - Clean and de-scale heat exchanger.

8 - Ensure high limit is set correctly so that power to the valve will be restored when the temperature returns to a low enough value.