nl en de
Selecteer uw gewenste taal

In welk land bevindt uw cv ketel zich?

Storingen


Ketel type Trinity TX200C

Storingscode Err 61

Oorzaak:

Return Sensor Error

Oplossing:

Inlet temperature exceeded 203⁰F; error clears when inlet temperature drops below 190⁰F: (1) ensure there is water flow through the boiler, (2) check for correct return sensor reading, (3) check wiring to return sensor; replace sensor