nl en de
Selecteer uw gewenste taal

In welk land bevindt uw cv ketel zich?

Storingen


Ketel type Trinity Fire Tube (Tft110)

Storingscode Lockout 79

Oorzaak:

1. CH or DHW settings
2. CH or DHW pump problem
3. Incorrect “Outlet high limit” setting
4. Incorrect “Outlet high limit response” setting

Oplossing:

1. Check if CH and/or DHW setpoint temperature plus off hysteresis exceed “High limit” setpoint – factory setting = 200°F (93°C).
2. See "Inoperative CH or DHW pump" below.
3. Increase “Outlet high limit” setting; maximum setting = 200°F (93°C).
4. Unless deemed unacceptable by local installation codes, the “Outlet high limit response” should be set to “recycle and hold” to prevent lockout.