Boiler type SSV-075

Error code A18

Cause:

High Temperature opens during normal operation

Solution:

1. Disconnect harness from high temperature supply switch and control module J13. Check continuity of both purple wires. Continuity available for both purple wires? 
Yes: -> 2
No: Replace wire(s) 

2. Is supply water temperature less than 185°F (91°C)? 
Yes: -> 3
No: -> 4

3. Is high temperature supply switch open? 
Yes: Replace high temperature supply switch
No: -> 5

4. Is high temperature supply switch open? 
Yes: Replace high temperature supply switch
No: Replace control module

5. Measure resistance across high temperature supply switch terminals 2 and 4? Does resistance match supply water temperature? 
Yes: Replace control module.
No: Replace high temperature Supply switch