nl en de
Select your language

Select country

Errors


Boiler type UBSSC-299

Error code E52

Cause:

Return water temperature sensor is open. No continuity.

Solution:

1. Is harness plugged into return temperature sensor? Is harness plugged into control module J5? 
Yes: -> 2 
No: Insert harness 

2. Check continuity of brown wires between return temperature sensor and control module J5-4 and J5-12 continuity? 
Yes: -> 3
No: Replace wires 

3. Measure return temperature sensor resistance with digital meter. Estimate sensor temperature. Does temperature fall within ranges? 
Yes: Replace control module.
No: Replace return temperature sensor.