Boiler type UBSSC-200

Error code E36

Cause:

Low water cutoff sees no water. 

Solution:

1. Check low water cutoff. Is amber lamp fit? 
Yes: Repair system piping, remove any remaining air in system 
No: -> 2

2. Check low water cutoff. Is green power lamp fit? 
Yes: -> 3
No: -> 5

3. Is harness plugged into control module J16? 
Yes: -> 4
No: Insert Harness

4. Disconnect harness from low water cutoff and control module J16. Check continuity if harness. Harness OK? 
Yes: Replace low water cutoff
No: Replace harness

5. Is Harness plugged into low water cutoff? Is blue/yellow harness plugges into 24Vac transformer? Is black/white harness plugged into 24volt harness? 
Yes: -> 6
No: -> Insert harness

6. Disconnect blue/yellow harness from transformer. Using digital meter check for 24 Vac. Is 24 to 30 Vac present? 
Yes: -> 7 
No: -> 8

7. Connect harness to transformer. Disconnect harness from low water cutoff. Is 24 Vac at terminals 1 and 2 ( between blue and yellow wires)? 
Yes: Replace low water cutoff 
No: Replace harness 

8. Disconnect black/white harness from transformer. Is 120 Vac measured at harness? 
Yes: Replace transformer
No: Replace main harness