nl en de
Select your language

Select country

Errors


Boiler type PVG-3

Error code STA15

Cause:

Limit Open

 

Solution:

Waiting for Limit to Open.
-Check Flame Rollout Switch, in the event of excessive blockage of the boiler section flue passageways is developed the flame rollout switch will open interrupting power to control P5-4. The main burners will be extinguished immediately and the circulator will remain on until the thermostat is turned off.  If the flame rollout switch is activated, do not attempt to place the boiler in operation.  The source of the  blockage must be corrected and the identical flame rollout switch replaced by trained and skilled personnel from a qualified service agency.
-Check External Limit.