Boiler type Greenstar ZWB35-3A

Error code d5

Cause:

External supply temperature sensor defective (low-loss header).
The external supply temperature sensor was recognized on the BUS and then reconnected to the appropriate terminal.

Solution:

Check temperature sensor and leads for interruptions or shorts, and replace if defective.
Check whether only one temperature sensor is connected; otherwise remove second temperature sensor.
Reset the boiler to the factory default settings ( service function 8.E), reset the IPM 2 (if installed) to the factory default settings and carry out the automatic system configuration.