nl en de
Select your language

Select country

Errors


Boiler type WBCETNG750

Error code TEMPER BLOCKING PRIO

Cause:

This screen indicates a demand for heat from the DHW circuit. The pump is powered on and the supply sensor temperature is too high for the boiler to ignite. This occurs because the water temperature measured by the supply sensor is higher than the tank temperature – ignition diff setting.

Solution:

This message will stay present until the water temperature measured by the supply sensor is less than the BOILER SUPPLY – boiler supply differential (5oF) or DHW SETPOINT is satisfied and no longer calls for heat.