Boiler type CHS-399

Error code Hold 95

Cause:

Stack sensor fault

1. Sensor disconnected. 
2. Faulty sensor

Solution:

1. Check sensor connection located at the bottom of the flue pipe inside the boiler cabinet. Check connection on control board.
2. Check resistance of sensor and compare to thermistor resistance chart.