nl en de
Select your language

Select country

Errors


Boiler type Magnatherm MGV4000

Error code 156

Cause:

Combustion pressure and flame ON

Solution:

- Check that flame is not present in the combustion chamber. Correct any errors.
- Make sure that the flame detector is wired to the correct terminal.
- Make sure the F & G wires are protected from stray noise pickup.
- Reset and sequence the module, if code reappears, replace the flame detector.
- Reset and sequence the module, if code reappears, replace the module.