Boiler type MARQUIS TWH200

Error code 94

Cause:

Exhaust NTC detects Vent Temperature is Greater than 149°F (65°C) 

Solution:

This Error Code will go away when the condition is remedied. If Error happens again:
1. Check if dip switch High Fire setting is ON. Switches 6 and 7 should be OFF for normal operation.
2. Check exhaust temperature sensor. Ensure connections are secure.
3. Check sensor resistance. If resistance is zero, replace the sensor.
4. Check exhaust vent for blockage.
5. If the problem persists, replace the control.
6. If the problem persists, replace the heat exchanger. * In Case Of PVC Vent Setting, Exhaust NTC detects Vent Temperature is Greater than 149°F (65°C)