Kessel Typ Alpine Alp285B

Störungscode 19

Ursach:

Purge rate proving failed

Blower is not running at Purge rate when it should or blower speed signal not being detected by Sage2.1.

LÖsung:

-Loose connection in 120 VAC blower wiring.
-Loose or miswired blower speed harness.
-Defective blower