Kessel Typ CH-180 ASME

Störungscode E030

Ursach:

Exhaust Overheat: exhaust high limit switch shuts down the unit when the flue temperature exceed 149°F (65°C).

LÖsung:

Turn OFF the system for at least 30 minutes then restart.
Clean the DHW cold water inlet filter.
Check the heat exchanger; remove and clean with a cleaning solution.