Störungen / Fehler


Kessel Typ Cadet CDN100

Störungscode n03

Ursach:

The fan speed is being limited due to the temperature rise across the heat exchanger exceeding 55°F.

LÖsung:

- Verify that the system is full of water and that all air has been properly purged from the system.

- Verify that the boiler is piped properly into the heating system.

- Check for 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary.

- If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump.

- Verify that the boiler pump is set to the proper speed or that the pump is the proper size.