Störungscode Err 61

Ursach:

Return Sensor Error

LÖsung:

Inlet temperature exceeded 203⁰F; error clears when inlet temperature drops below 190⁰F: (1) ensure there is water flow through the boiler, (2) check for correct return sensor reading, (3) check wiring to return sensor; replace sensor