Störungen / Fehler


Kessel Typ Helix VX-200

Störungscode E52

Ursach:

Return water temperature sensor is open. No continuity.

LÖsung:

1. Is harness plugged into Return Temperature Sensor? Is harness plugged into Control Module J5?
Yes: -> 2
No: Insert harness

2.Check continuity of brown wires between Return Temperature Sensor and Control Module J5-4 and J5-12 Continuity?  
Yes: -> 3
No: Replace Wires

3. Measure return temperature sensor resistance with digital meter. Estimate sensor temperature. Does temperature fall within ranges shown on chart? 
Yes: Replace control module
No: Replace retun temperature sensor