nl en de
Selecteer uw gewenste taal

In welk land bevindt uw cv ketel zich?

Storingen


Ketel type Trinity Lx500

Storingscode Lockout 113

Oorzaak:

A flame circuit shorted to ground may show up as a flame circuit timeout. High resistance shorts can display as Lockout 113. 

Oplossing:

Check to ensure condensate drain is not blocked. Check to ensure no voltage applied to R & CH terminals. If using 4-20mA input, check to ensure current is not greater than 21mA.