nl en de
Select your language

Select country

Errors


Boiler type SSV-050

Error code E65

Cause:

Flue temperature sensor is shorted. '0' Ohm 

Solution:

1. Disconnect wire harness from vent temperature sensor. Measure sensor resistance. Does resistance match estimate flue temperature? 
Yes: -> 2
No: Replace vent temperature sensor. 

2. Disconnect harness from control module J5. Continuity in blue wires? 
Yes: Replace controle module.
No: Replace wires.