nl en de
Select your language

Select country

Errors


Boiler type Brute Elite BNTV-399

Error code 156

Cause:

Combustion pressure and flame On

Solution:

-Check that flame is not present in the combustion chamber. Correct any errors.
-Make sure that the flame detector is wired to the correct terminal.
-Make sure the F & G wires are protected from stray noise pickup.
-Reset and sequence the module, if code reappears, replace the flame detector.
-Reset and sequence the module, if code reappears, replace the module.