Boiler type E110CN

Error code bl85

Cause:

No water flow can be detected through the controller. De-aeration cycle is started. When water flow is detected during this cycle, the de-aeration cycle is terminated and the burner is released. The controller checks the water pressure during static and dynamic situation.

Solution:

Check the installation for the presence of air;If there is a secondary pump installed and it is not hydraulicly separated, it could cause pressure differences. Check the use of balancing valves.

-Check if the pump is functioning and/or that the water pressure sensor is 
working properly;
Polluted pump;
Polluted water pressure sensor;
Polluted water filter;
Wiring of pump.