nl en de
Select your language

Select country

Errors


Boiler type Bimini BWC120

Error code b24

Cause:

 

MCBA is reading a return sensor temperature higher than the supply sensor temperature.
Condition must be present for at least 75s for this error code to appear. 

Solution:

 

• Flow through boiler reversed. Verify correct piping and pump orientation.
• No boiler water flow. Verify that system is purged of air and that appropriate  valves are open.
• Sensor wiring reversed.
• Supply or return sensor defective.