Boiler type Helix VX-150

Error code A18

Cause:

High Temperature opens during normal operation.

Solution:

1. Disconnect harness from High Temperature Supply Switch and Control Module J13. Check continuity of both purple wires. Continuity available from both purple wires? 
Yes: -> 2
No: Replace wire)s) 

2. Is supply water temperature less than 185ºF ( 91ºC)?
Yes: -> 3
No: -> 5

3. Is high temperature supply switch open? 
Yes: Replace high temperature supply switch
No: -> 4

4. Measure resistance across high temperature supply switch terminals 2 and 4? Does resistance match supply water temperature? 
Yes: Replace control module
No: Replace high temperature supply switch.

5. Is high temperature supply switch open? 
Yes: Replace high temperature supply switch
No: Replace control module