Boiler type Helix VX-150

Error code A05

Cause:

Open gas valve power circuit. May involve high temperature switch, gas valve, or gas valve relay in control module.

Solution:

1. Unplug connector on supply sensor. Measure continuity of high limit sensor (close/open signal) between two pins connected to two purple wires. Is continuity available?
Yes: -> 2
No: -> 4

2. Is wire harness connected to both Gas Valve and J13 connector on Control Module?
Yes: -> 3
No: Connect harness

3. Disconnect J13 connector on gas valve. Measure resistance across top and bottom pins (1 & 5). Is resistance between 1.0 and 1.2 kΩ? 
Yes: Replace Control Module 
No: -> 5

4. Is supply pipe (copper pipe at top of boiler) hot?
Yes: Boiler has been dry fired. System has too much air. Close manual gas valve (shut off gas). Purge air from system, wait for system to cool.
No: Replace Supply Sensor

5. Disconnect harness from Gas Valve. Does each wire have continuity between Gas Valve and Control Module.
Yes: Replace Gas Valve
No: Replace Harness