nl en de
Wähle Ihre Sprache

Land wählen

Störungen / Fehler


Kessel Typ QP85N

Störungscode E12

Ursach:

High limit stat open.

LÖsung:

Supply temperature too high. Caused by
-Presence of air
-Possible polluted impeller of the circulation boiler pump
-Polluted internal filter

Check de-aerator. Replace when necessary the automatic de-aerator and restart boiler for de-aerating programm (17min.)

Check water fl ow over system. Clean when necessary the pump and or filter. Flush complete system

Check adjustment of balancing valves