Kessel Typ GWM-050IE

Störungscode E44

Ursach:

Phase error

LÖsung:

1. Measure incomming power with volt meter. Is terminal 120 Vac (L) approximately 120 Vac? Is 120 Vac (N) approximately 0 Vac? 
Yes: -> 2.
No: Correct power supply to boiler.

2. Verify order of pins on J2. 4 pins order should be: empty, black ( or red), white, green. Measurevolts on pins of black wire and white wire. Is wiring/pins in right order? Does black/white wire pin have 0 Vac? 
Yes: Replace control module.