nl en de
Wähle Ihre Sprache

Land wählen

Störungen / Fehler


Kessel Typ WBRUNG120W

Störungscode Er:10

Ursach:

Flame has Extinguished 8 (Eight) Times

LÖsung:

Press the Power button to clear the Error Code.
If Error happens again:
- Monitor the gas pressure to the boiler while in operation. Ensure pressure is between 3.5 and 14” WC.
- Check gas valve wire. Ensure connection is secure.
- Check flame detection sensor. Ensure connections are secure. Normal operating settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
- Check vent terminations. Ensure there are no blockages.
- Assure that the flame is stable when lit.
- If the problem persists, replace the main control.